| MODEL |
AD1000(L) |
AD2000(L) |
AD3000 (L) |
| PHASE |
Single phase with ground |
| CAPACITY* |
1000 VA / 800 W |
2000 VA / 1600 W |
3000 VA / 2400 W |
| INPUT |
| Nominal Voltage |
200/208/220/230/240VAC |
| Input Voltage Range |
55-150 VAC or 110-300 VAC(Based on load at 50%) |
| 85-140VAC or 160-280VAC (Based on load at 100%) |
| Frequency Range |
40 Hz ~ 70 Hz |
| Power Factor |
0.99 @ Nominal Voltage (100% load) |
| OUTPUT |
| Output Voltage |
200/208/220/230/240VAC |
| Voltage Regulation |
+1% |
| Frequency Range (Synchronized Range) |
47~ 53 Hz or 57 ~ 63 Hz |
| Frequency Range (Batt.Mode) |
50 Hz + 0.25 Hz or 60Hz + 0.3 Hz |
| Current Crest Ratio |
3:1 |
| Harmonic Distortion |
3 % THD (Linear Load) |
| 6 % THD (Non-linear Load) |
| Waveform (Batt.Mode) |
Pure Sine wave |
| EFFICIENCY |
| AC Mode |
88% |
89% |
90% |
| Battery Mode |
83% |
87% |
88% |
| BATTERY |
| Battery Type |
12 V / 9 Ah |
12 V / 9 Ah |
12 V / 9 Ah |
| Numbers |
2 |
4 |
6 |
| Typical Recharge Time |
4 hours recover to 90% capacity |
| Charging Current (max.) |
1A |
| Charging Voltage |
27.4VDC +1% |
54.7 VDC +1% |
82.1 VDC +1% |
| INDICATORS |
| LCD |
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
| ALARM |
| Battery Mode |
Sounding every 4 seconds |
| Low Battery |
Sounding every second |
| Overload |
Sounding twice every second |
| Fault |
Continuously sounding |
| ENVIRONMENT |
| Humidity |
20-90 % RH @ 0- 40(Non-condensing) |
| Noise Level |
Less than 50dB @ 1 Meter |
| MANAGEMENT |
| Smart RS-232 / USB |
Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux and MAC |
| Optional SNMP |